Model: PG-2000
pg2000capum45.DOC Rev: 4.5
- 15 -
6.0 SETTINGS SHEET
Checked by
Model Number
Serial Number
Hardware Rev.
Software Rev.
The factory settings column below lists the typical default settings. The user may change these values. If
changed, please fill in the USER SETTING column for future reference.
PARAMETER DESCRIPTION
FACTORY
SETTING
USER
SETTING
Number of Sensors
Total number of sensors in the system
Number of Zones Total number of zones
Zone 1(eg.1-6)
Zone 2(eg.7-12)
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone
configuration
( Sensor numbers
per Zone)
Zone 8
GAS ALARM / mA SPAN
Code
0 = CO
Low Alarm high threshold – concentration of any EC
Gold transmitter in the zone must exceed this value for
at least the the Low Alarm delay to ON period to activate
the Low Alarm.
Low Alarm low threshold – concentration of all EC Gold
transmitters in the zone must fall below this value for at
least the Low Alarm delay to OFF period to de-activate
the Low Alarm
High Alarm high threshold. As per Low Alarm
thresholds description
High Alarm low threshold. As per Low Alarm
thresholds description.
High High Alarm high threshold. As per Low Alarm
thresholds description
GAS #1 ALARM
Alarms may be
set for up to 4
gases. Alarms
are checked
based on the gas
type setting in EC
Gold Transmitters.
For example, in a
system with EC
Gold transmitters
for CO and NO2,
enter separate
alarm values for
CO (Gas #1) and
for NO2 (Gas #2).
Gases #3 and #4
are set to
UNUSED
High High Alarm low threshold. As per Low Alarm
thresholds description
SPAN
This is used if ordered in place of enclosure mounted
buzzer. Must be ordered at time of order. This is also
used on the optional Auxillary Board. There are up to 2
per board to reflect the maximum gas concentration in
the zone. The full Scale concentration in ppm.